P 26.2

Differential pressure transmitter P 26.2 with scalable measuring range and a high level of overpressure protection

Overview
Technical data
Downloads
Images

Pressure Transmitter with High Accuracy, Scalable Measuring Range, and High Overload Protection

Special features

  • High-precision differential pressure transmitter for cleanroom, HVAC, and process technology
  • Precisely matched measuring ranges starting at 10 Pa, uni- and bidirectional
  • No zero-point drift thanks to automatic zero-point adjustment
  • Easy commissioning and flexible installation (top-hat rail and wall mounting)
  • Multiple switching and analog outputs as standard
  • Extensive configuration via parameterization software through internal USB-C interface

The P 26.2 pressure transmitter is particularly suitable for pressure monitoring in cleanrooms, laboratories, pharmaceutical facilities, operating rooms, as well as for special applications in mechanical and plant engineering. In addition to differential pressure, the device also measures positive and negative overpressure as well as flow velocity or volume flow. The measuring ranges are scalable from 10 to 100%. A selectable time constant allows optimal adaptation of the transmitter to the pressure conditions, ensuring a stable output signal. The pressure transmitter is CE-certified as standard and available with NRTL certification according to UL / CSA 61010-1.

Options

  • Available with a factory calibration certificate or a calibration certificate in accordance with DKD Guideline 6-1
  • M12 connectors instead of cable glands
  • Selectable power supply: 24 V AC/DC with or without galvanic isolation, or mains voltage 100 V – 240 / 277 V
  • Various pressure connections
  • Display with buttons for local configuration
  • Two optional relays enable the connection of mains-powered alarms when limit values are exceeded or not met
  • T- or P-/T-compensation for precise volume flow measurement, including air consumption meters
Measurement ranges
10 / 50 / 100 / 200 / 250 / 500 Pa1 / 2.5 / 5 / 10 / 20 / 50 / 100 kPaFreely scalable from 10..100% within a measurement rangeOthers available upon request
Measurement accuracy
± 0.2 % FS for measurement ranges ≤ 50 kPa± 0.5 % FS
Output signal
0 .. 10 V (RL ≥ 2 kΩ)0 .. 20 mA (RL ≤ 500 Ω)4 .. 20 mA (RL ≤ 500 Ω)
Interface
USB-C portUSB-C, data cable in scope of deliveryExternal zeroing
Display

Multi-coloured LCD and keyboard (optional)

Protection class

IP 65

Pressure connections

Grommet for 4/6 mm tubing, 2 x laboratory nozzle DIN 12898, Plug-in fitting 4, 6 und 8 mm, Compression ring fitting 6 und 8 mm

Contact points
Potential-free semiconductor switches (2x NO contact)Potential-free relay (2x changeover contact) optionalAir consumption meter (optional)
Power supply
24 VAC, ± 10 % with galvanic separation24 VAC/DC, ± 10 %100 .. 240/277 VAC, ± 10 %
Data sheets with technical drawing

Similar products

Find contact

Sharing your user data with third parties

We use cookies on this website. Details on cookie types, their purpose and third parties involved are described in our Privacy Policy. Please click "Accept all" to agree to the use of all cookies as described in our Privacy Policy. You can also reject individual cookies by clicking on "Manage".

We are here for you

nfhlstrp-wlchrd+49 76 61 39 63 0Product requestRepair requestCalibration requestDistributors

List of bookmarked items

Your web browser is out of date. Update your browser for more security, speed and the best experience on this site.

Update browser